products show

HFC-227EA Automatic Fire Suppression System

1.        System Introduction
HFC-227ea fire extinguishing-agent ,CF3CHFCF3 which is a clean, low toxic, isolated, effective product which makes no damages to the ozonosphere, it is a successfully developed gaseous fire-extinguishing agent until today. HFC-227ea is one of good replacement for the Halon fire extinguishing-agents.
HFC-227ea is effective with fully-immersing way to put out electrical fire, flammable liquid or soluble solid fire, solid surface fire, and gas fire which supply can be cut down before extinguishing. It is to be used in place with people working or gathering. HFC-227ea leaves no residua and is conducting medium free, these features make HFC-227ea irreplaceable in locations such as computer room, telecom machine room, power transmission room, Precision apparatus room, power room, gas and oil terminal, flammable chemical and book storage, document and file storage, gold vault, etc.

Not suitable for extinguishing following fire
1.        Oxidizing Chemical and mixture , such as
2.        activitly metal ,such as potassium(K), magnesium(Mg), Zirconium( Zr) , Uranium (U),etc.
3.        Metal hydroxide , Potassium hydride , Sodium hydride
4.        Miscellaneous fire caused by decomposition Chemical ,Such as Hydrogen oxide,  
 
Design According to following Standard :
CHINA GB795. GB79G , GB410, GB14104 , NFPA-2001(U.S.A)
GA400-2002<<Testing Way and Performance of extinguishing system Parts >>
 
Main Specifications and parameter of system :
Fire Extinguishing Means: Total flooding and fully-immersing
System design working pressure : 4.2Mpa
System operation max. working pressure : 5.3Mpa ~ 5.4Mpa
System operation min.Working pressure: 3.6Mpa
Design pressure of the Nozzle:  Normal ≥0.7Mpa , Min.≥0.40Mpa
Single Nozzle protection radius: ≤5M
Single Nozzle protective height; ≤5M
Discharging time : ≤10S
Working temperature: -0℃~+50℃
Gas filling rate( density) : ≤1.15kg/L
System start ways : Automatic Control , Pneumatic Manual and Emergency Manual Control
Gas storage cylinder ; 20Ltr, 30Ltr, 40Ltr, 60Ltr , 70Ltr , 100Ltr, 120Ltr,150Ltr, 180Ltr , 250Ltr other details see details of the cylinder
Power Supply : DCV 24 , 0.5A
Max Protective Area : 8 Zones (depend on designs)